Korelasi Jenis Belitan Trafo Terhadap Nilai Setting Relai Proteksi Differensial Berbasis Transformasi Wavelet Paket

No Thumbnail Available

Date

2016-02-25

Authors

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

This paper describe correlation between various three phase power transformer winding with wavelet transform based differential relay setting value. The WPT is employed to obtain the characteristics of power transformer fault currents so that the type of faults can be determined. The algorithm is able to distinguish internal faults and normal condition as well as magnetizing inrush. The algorithm is tested for protecting various winding of power transformer. To reach good performance of the algorithm, hence relay setting value should be changed according to power transformer type. For various three phase power transformer winding Y- , Y-Y, - , and, -Y, hence the relay setting value are 12.10-2, 15.10-2, 4.8.10-2 and, 7.10-2 respectively.

Description

Keywords

Wavelet packet transforms, three phase power transformer, differential protection, magnetizing inrush, relay setting value