Comparative Study of Residential Split Air Conditioner as Water Heater (RSACWH) Using R-22 and HCR-22 Refrigerant
dc.contributor.author | Aziz, Azridjal | |
dc.contributor.author | Thalal | |
dc.contributor.author | Mainil, Rahmat Iman | |
dc.contributor.author | Mainil, Adfhal Kurniawan | |
dc.date.accessioned | 2016-04-19T02:43:48Z | |
dc.date.available | 2016-04-19T02:43:48Z | |
dc.date.issued | 2016-04-19 | |
dc.description.abstract | Experimental studies on Residential Split AC Water Heater (RSACWH) by replacing refrigerant R-22 with HCR-22 (hydrocarbon refrigerants) as a drop-in substitute has been carried out. The dummy condenser (trombone type coil) as heat recovery system was used for heating water and installed in the water tank with 50 L capacity. The use of HCR-22 save electrical energy due to decrease in compressor power about 16.31% - 21.64% of the R-22, because HCR-22 refrigerant mass charge in the refrigeration system 40% less than the charge of R-22. The cooling capacity and heat rejection capacity is relatively the same for R-22 and HCR-22. The COPR increases around 11.89% - 18.69% and COPR + HP also increases around 4.26%-11.41% for HCR-22 compared to R-22. The room temperature with HCR-22 is relatively the same compared to R-22, while the hot water temperature using HCR-22 and R-22 are about 46.58°C-48.81°C and 59.50°C-63.40°C respectively. The use of the HCR-22 provides electrical energy savings for compressor power and better performance (COP) at similar room temperature compared to R-22. | en_US |
dc.description.sponsorship | he 2nd International Conference on Ocean, Mechanical & Aerospace -scientists & engineers (OMASE 2015) | en_US |
dc.identifier.issn | 2443-1710 | |
dc.identifier.other | wahyu sari yeni | |
dc.identifier.uri | http://repository.unri.ac.id/xmlui/handle/123456789/8208 | |
dc.language.iso | en | en_US |
dc.subject | water heater | en_US |
dc.subject | hydrocarbon refrigerant | en_US |
dc.subject | trombone coil | en_US |
dc.subject | dummy condenser | en_US |
dc.subject | heat recovery | en_US |
dc.title | Comparative Study of Residential Split Air Conditioner as Water Heater (RSACWH) Using R-22 and HCR-22 Refrigerant | en_US |
dc.type | UR-Scientific Work Lecturer | en_US |
Files
Original bundle
1 - 3 of 3
No Thumbnail Available
- Name:
- cover.pdf
- Size:
- 164.55 KB
- Format:
- Adobe Portable Document Format
- Description:
- COVER
No Thumbnail Available
- Name:
- daftar isi.pdf
- Size:
- 129.05 KB
- Format:
- Adobe Portable Document Format
- Description:
- daftra isi
No Thumbnail Available
- Name:
- 18b Proc OMASE 2015 2-1-13.pdf
- Size:
- 1.26 MB
- Format:
- Adobe Portable Document Format
- Description:
- artikel
License bundle
1 - 1 of 1
No Thumbnail Available
- Name:
- license.txt
- Size:
- 1.71 KB
- Format:
- Item-specific license agreed upon to submission
- Description: