dc.contributor.author |
Iswadi |
|
dc.date.accessioned |
2016-02-25T04:20:06Z |
|
dc.date.available |
2016-02-25T04:20:06Z |
|
dc.date.issued |
2016-02-25 |
|
dc.identifier.issn |
1907-0500 |
|
dc.identifier.other |
wahyu sari yeni |
|
dc.identifier.uri |
http://repository.unri.ac.id/xmlui/handle/123456789/7969 |
|
dc.description.abstract |
This paper describe correlation between various three phase power transformer winding with wavelet
transform based differential relay setting value. The WPT is employed to obtain the characteristics of
power transformer fault currents so that the type of faults can be determined. The algorithm is able to
distinguish internal faults and normal condition as well as magnetizing inrush. The algorithm is tested
for protecting various winding of power transformer. To reach good performance of the algorithm,
hence relay setting value should be changed according to power transformer type. For various three
phase power transformer winding Y- , Y-Y, - , and, -Y, hence the relay setting value are 12.10-2,
15.10-2, 4.8.10-2 and, 7.10-2 respectively. |
en_US |
dc.description.provenance |
Submitted by wahyu sari yeni (ayoe32@ymail.com) on 2016-02-25T04:20:06Z
No. of bitstreams: 1
E09.pdf: 994850 bytes, checksum: a13720970cc9950ee33a3609fb86d4c6 (MD5) |
en |
dc.description.provenance |
Made available in DSpace on 2016-02-25T04:20:06Z (GMT). No. of bitstreams: 1
E09.pdf: 994850 bytes, checksum: a13720970cc9950ee33a3609fb86d4c6 (MD5) |
en |
dc.description.sponsorship |
Seminar Nasional Teknik Kimia Oleo & Petrokimia Indonesia 2008 |
en_US |
dc.language.iso |
en |
en_US |
dc.subject |
Wavelet packet transforms |
en_US |
dc.subject |
three phase power transformer |
en_US |
dc.subject |
differential protection |
en_US |
dc.subject |
magnetizing inrush |
en_US |
dc.subject |
relay setting value |
en_US |
dc.title |
Korelasi Jenis Belitan Trafo Terhadap Nilai Setting Relai Proteksi Differensial Berbasis Transformasi Wavelet Paket |
en_US |
dc.type |
UR-Proceedings |
en_US |